● Free-to-set display and output correspondence, easy to copy frequency/speed/pressure/opening;
● Output 0-10V, 0-20mA, 2-10V, 4-20mA can be directly selected;
● All parameters are saved after power failure. "Given output" can select whether to save after power failure (set by F0-8);
● Multiple given modes can be selected. Check FO-2 parameter for details;
● Convenient for applications requiring slow changes;
● Add automatic operation function, one key off output and other functions.
● Cooperate with various analog output sensors and transmitters;
● Measurement, transformation, display;
● Control of temperature, pressure, liquid level, composition and other physical quantities.
● XDB 904 digital display meter designed for displaying physical quantities such as temperature, pressure, and liquid level.
1. FO Parameters Value -Display parameters
Code | Parameters | Description | Default | R/W |
FO-O | Data acquisition value monitoring | Monitor the percentage of current analog signal input value, range 0-100 % | — | Read only |
FO-1 | Display value monitor | Display value, calculated by F0・0, FO-2, FO-3, FO-4 below | — | Read only |
FO-2 | Display accuracy | The decimal points setting for the display value, available points value: 0-3 | 1 | Read/write |
FO-3 | Min. display value | Display the 0% of the corresponding data acquisition value, range: -1999-9999 | 0 | Read/write |
FO-4 | Max. display value | Display the 100% of the corresponding data acquisition value, range: -1999-9999 | 1000 | Read/write |
2. Fl Parameters Value-Analog signal configuration parameters
Code | Parameters | Description | Default | R/W |
Fl-0 | Input type selection | 0: 0-10V or 0-20mA input in corresponding to 0-100.0%1: 2-10V or 4-20mA input in corresponding to 0-100.0% (lower than 0V or 4mA displays 0) | 0 | Read/write |
Fl-1 | Input filtering time | Range: O-lO.OOOs, filtering time is longer, the filtering effect is better. | 0.200 | Read/write |
Fl-2 | Input gain | Range: 0-1000.0% | 100.0 | Read/write |
Fl-3 | Input offset | -99.9-99.9%, 10V/20mA ―100% | 0.0 | Read/write |
Fl-4 | On hold | None | 0 | Read/write |
Fl-5 | Parameters setting selection | 0: long pressing SET button for 3s to enter parameters setting mode; 1: keep pressing SET button for 3s and pressing OK button to enter parameters setting mode. | 0 | Read/write |