1.DC7-30V
2.Relay output contact isolation
3.Communication interface supports RS485 or RS232
4.Communication baud rate: 2400, 4800, 9600, 19200, 38400 (can be modified by software, default 9600
5.Communication protocol: support standard modbus RTU protocol
6.0-255 device addresses can be set, 5-bit address dip switch can set 1-31 address codes, greater than 31 can be set by software
7.With flash on and flash off function, you can bring parameters in the command, operate the relay to open for a period of time and automatically close
8.With strobe function, the controller relay can be periodically switched on and off
Serial number |
Pin |
Description |
1 |
+ |
Positive power supply |
2 |
- |
Negative power supply |
3 |
VIN |
For passive input, VIN and COM are short-circuited. Please refer to the input wiring diagram for details |
4 |
COM+ |
For passive input, VIN and COM are short-circuited. Please refer to the input wiring diagram for details |
5 |
IN1 |
First switch input |
6 |
IN2 |
Second switch input |
7 |
IN3 |
Third switch input |
8 |
IN4 |
Fourth switch input |
9 |
COM- |
Used for passive input, see input wiring diagram for details |
10 |
Normally open |
The first relay output is normally open |
11 |
Common terminal |
The first relay output is common |
12 |
Normally closed |
The first relay output is normally closed |
13 |
Normally open |
The second relay output is normally open |
14 |
Common terminal |
The second relay output is common |
15 |
Normally closed |
The second relay output is normally closed |
16 |
Normally open |
The third relay output is normally open |
17 |
Common terminal |
The third relay output is common |
18 |
Normally closed |
The third relay output is normally closed |
19 |
Normally open |
The fourth relay output is normally open |
20 |
Common terminal |
The fourth relay output is common |
21 |
Normally closed |
The fourth relay output is normally closed |
RS485 cascade wiring method
The computer's built-in serial port is usually RS232, which requires a 232-485 converter (active and isolated converters are recommended for industrial environments). After conversion, RS485 is divided into two wires, A and B. A is connected to the A terminal on the board, and B is connected to the B terminal on the board. The 485 shield can be connected to GND. If there are many devices, it is recommended to use twisted shielded cables and a chain network structure.
Input and output wiring
Relay Wiring Instructions
Output wiring
1.General Relay Wiring Instructions
2. AC 220V equipment wiring
3. AC 380V equipment wiring
4. 380V equipment wiring without neutral line
5. Wiring of equipment below DC 30V
Input wiring
1. Wiring diagram of active switch (NPN type low level)
2. Passive switch quantity (dry contact) wiring diagram